How to calculate the current of a 100 KVA transformer with a rating of 11kV/433V.
I = (KVA x 1000) / (√3 x V)
where:
I = current in amperes
KVA = apparent power rating of the transformer in
kilovolt-amperes (100 KVA in this case)
V = rated voltage of the transformer (433V in this case)
√3 = square root of 3 (1.732)
For a 11kV/433V transformer, we need to determine the
primary current and the secondary current separately.
Primary Current:
The primary voltage is 11kV. Assuming a three-phase
connection, we can calculate the primary current as follows:
I1 = (KVA x 1000) / (√3 x V1)
where:
I1 = primary current in amperes
KVA = apparent power rating of the transformer in
kilovolt-amperes (100 KVA in this case)
V1 = primary voltage of the transformer (11kV in this case)
√3 = square root of 3 (1.732)
Substituting these values in the formula, we get:
I1 = (100 x 1000) / (1.732 x 11000) = 5.46 amperes
(approximately)
Therefore, the primary current of the 100 KVA transformer
with a rating of 11kV/433V is approximately 5.46 amperes.
Secondary Current:
The secondary voltage is 433V. We can calculate the
secondary current as follows:
I2 = (KVA x 1000) / (√3 x V2)
where:
I2 = secondary current in amperes
KVA = apparent power rating of the transformer in
kilovolt-amperes (100 KVA in this case)
V2 = secondary voltage of the transformer (433V in this
case)
√3 = square root of 3 (1.732)
Substituting these values in the formula, we get:
I2 = (100 x 1000) / (1.732 x 433) = 129.1 amperes
(approximately)
Therefore, the secondary current of the 100 KVA transformer
with a rating of 11kV/433V is approximately 129.1 amperes.
It's important to note that the actual current may vary depending on various factors such as the load, power factor, and other transformer characteristics.